These requirements cover steel welded outlet fittings intended
for use in water based fire protection systems in accordance with
the following installation standards:
a) Standard for Low-, Medium-, and High-Expansion Foam, NFPA 11;
b) Standard for the Installation of Sprinkler Systems, NFPA 13;
c) Standard for the Installation of Sprinkler Systems in One-
and Two-Family Dwellings and Manufactured Homes, NFPA 13D;
d) Standard for the Installation of Sprinkler Systems in
Residential Occupancies Up to and Including Four Stories in Height,
NFPA 13R;
e) Standard for the Installation of Standpipe and Hose Systems,
NFPA 14;
f) Standard for Water Spray Fixed Systems for Fire Protection,
NFPA 15; and
g) Standard for the Installation of Foam-Water Sprinkler and
Foam-Water Spray Systems, NFPA 16;
Welded Outlet Fittings consist of steel outlets intended to be
welded to steel run pipe in Schedules 10, 30, 40 and Listed steel
sprinkler pipe having the same outside diameter as Schedule 40 pipe
where:
a) The outlet pipe having wall thickness the same as or less
than the run pipe or
b) The run pipe has a wall thickness equivalent to Schedule 10
steel pipe and the outlet wall thickness is equivalent to Schedule
40 steel pipe.
These fittings may be suitable for use with other Listed steel
run pipe when intended for use with outlet wall thicknesses greater
than the run pipe wall thickness, when evaluated as described in
Bending Moment Test, Section 11.