Description / Abstract:
These requirements cover devices intended for inter-connection
of equipment, sensors, and actuators in remote-control, signaling,
and power-limited circuits. Included are cable assemblies and
fittings, feeder-tap cable systems, feed-through connectors,
multi-outlet fittings, panel-mount fittings, and splitters. These
devices are not intended for disconnect means. These devices are
rated not more than 60 A and not more than 600 V.
Unless otherwise noted, all devices are intended for indoor
use.
These devices are for use on alternating current, direct
current, or both.
The cable assembly fittings and panel-mount fittings are
intended to be installed in accordance with the manufacturer's
installation instructions. The cable assembly fittings are intended
to be assembled or molded on flexible cord.
Each type of device covered by this standard is described in
generic terms where practicable. Reference to use locations
identified in the National Electrical Code or specific applications
are omitted unless they are required for the identification of the
device type. Such additional information is included in the
applicable standards for the end-use product involved or in
markings for the device.
This standard does not cover male-to-male cable assemblies.
This standard does not directly apply to the following but may
supplement other applicable standards:
a) Devices produced integrally with flexible cord or cable that
are covered by the Standard for Cord Sets and Power-Supply Cords,
UL 817;
b) Devices intended for connection to the branch circuit, such
as attachment plugs, cord connectors, receptacles, inlets, and
outlets, that are covered by the Standard for Attachment Plugs and
Receptacles, UL 498;
c) Devices solely intended for direct connection to the branch
circuit in accordance with the National Electrical Code, NFPA 70,
and that are provided with contacts of the pin and sleeve type,
covered by the Standard for Plugs, Receptacles, and Cable
Connectors, of the Pin and Sleeve Type, UL 1682;
d) Devices intended to interconnect industrial machinery and to
be installed in accordance with the Electrical Standard for
Industrial Machinery, NFPA 79 that are covered by the Outline of
Investigation for Multi-point Interconnection Power Cable
Assemblies For Industrial Machinery, Subject 2237;
e) Connectors intended for use in Data, Signal, Control and
Power Applications within and between electrical equipment and
intended for factory assembly as covered by the Standard for
Component Connectors for Use in Data, Signal, Control and Power
Applications, UL 1977; and the Standard for Telephone Equipment, UL
1459, or the Standard for Communications Circuit Accessories, UL
1863;
Fittings and devices that employ surge protective devices and/or
circuitry to provide surge protection of internal functionality, in
addition to complying with the requirements of this standard, shall
also comply with the construction and performance requirements for
Type 4 component assemblies or for Type 5 components, as
appropriate, in accordance with the Standard for Surge Protective
Devices, UL 1449.
Fittings and devices that are intended to provide surge
protection of connected equipment and wiring, in addition to the
requirements of this standard, shall also be evaluated to the
requirements (including ratings and markings) for either Type 2 or
Type 3 (surge protective devices) applications in accordance with
the Standard for Surge Protective Devices, UL 1449.