Description / Abstract:
This standard is comprised of six clauses. Clause 1 provides the
scope and purpose of this standard. Clause 2 lists references to
other standards, recommended practices, and guides that are useful
in applying this standard. Clause 3 provides definitions that are
either not found in other standards, recommended practices, and
guides, or have been modified for use with this standard. Clause 4
establishes the sample size and test parameters, while Clause 5
defines the acceptance criteria. Clause 6 describes the data
records that have to be maintained at the completion of the
test.
Scope
This standard applies to voltage-endurance testing of form-wound
stator winding bars and coils having a mica-based insulation system
with thermo-setting polyester and/or epoxy resins used in
hydrogenerators and pumped storage generators operating in air with
a rated line-to-line voltage between 4 000 to 22 000 V, and a
frequency of 50 Hz or 60 Hz.
Purpose
The purpose of this standard is to define the test parameters
for the voltage-endurance test and the number of specimens to be
used for each test. It also defines the acceptance criteria and the
procedures for retesting in the event of a premature failure during
the voltage-endurance test. The details of the test procedure are
described in IEEE Std 1043TM-1996.